Leave Your Message

China Factory Suppliers PC-WC Series Air Cooled Industrial Cold Water Machine for Low Temperature Cooling Solutions

,

Scope of Application

,

Introducing the advanced low temperature freezer, a top-tier refrigeration solution proudly manufactured by Manster Company. This innovative equipment is specifically designed for critical applications in pharmaceuticals, chemicals, and biotechnology. With a versatile temperature range adjustable from -30 degrees to +5 degrees, it meets the stringent requirements of various industries. Our low temperature freezer is equipped with a high-performance, imported compressor, ensuring exceptional cooling capacity and reliability. As one of the leading China suppliers, we are committed to delivering quality and efficiency, making us a trusted factory in the field of refrigeration technology.

,

    Design advantages

    1. Compact Structure & Smooth Operation

    Condenser and evaporator units use efficient heat transfer tubes. The host features imported, highly efficient hermetic scroll compressors, offering a compact structure, small size, and lightweight installation advantages. With fewer moving parts and flexible operation, it guarantees high energy efficiency, low noise, low operating costs, and high reliability. The continuous operation without pulse ensures stable performance, low noise, and minimal vibration. Efficiency is 20%-30% higher than reciprocating compressors.

    2. Improved Energy Control System

    Air conditioning units start and stop according to load changes for optimal energy efficiency. The computer control system dynamically adjusts energy output based on the client's thermal load changes. By monitoring the difference between the actual and set loads via microcomputer, the system quickly determines the required energy. Multi-system setups optimize output to ensure the lowest energy consumption, reflecting excellent performance at both full and partial loads.

    3. Simple & Intuitive Control

    Equipped with a microcomputer program controller (digital display) allowing users to start the unit with a simple touch of a button. The panel displays operating status and parameters in clear text at a glance. No professional training is required for normal operation. The system precisely controls temperature to 1℃ (special requests up to 0.1℃) within a set range of 5℃-50℃, facilitating direct analysis of the unit health.

    4. Microcomputer Protection Features

    Comprehensive protection features include compressor coil overcurrent protection, pump overcurrent protection, cold water flow switch, low cooling protection, high-temperature water protection, compressor overload protection, frequent start/stop protection, abnormal voltage protection, and high/low pressure protection.

    5. Multiple Protection, Safe & Reliable

    In addition to the internal compressor protection module providing over/under voltage, phase failure, and overload protection, the system integrates refrigeration pressure control units and other safety devices to make operation completely foolproof.

    6. Optimized Low-Noise Design

    Optimized refrigeration efficiency and design to reduce noise as much as possible, meeting strict environmental requirements. Air-cooled chiller pumps are easy to move and operate without requiring the installation of cooling towers.

    7. Easy to Install

    All components are pre-installed and run-tested at the factory, with refrigerants and refrigeration oils fully pre-charged. Users simply need to connect the water circuit and electrical circuit to put the system into immediate use, minimizing installation and commissioning time.

    Parameter Table (1)

    Type PC-3WC PC-4WC PC-5WC PC-6WC PC-8WC PC-10WC PC-12WC PC-15WC PC-15WC(D) PC-20WC(D)
    Refrigerating capacity Kcal/h
    50HZ/60HZ
    8170 11266 14018 16340 22532 28036 32680 43172 42140 56760
    Kcal/h (60HZ) 9804 13519 16822 19608 27038 33643 39216 51806 50568 68112
    KW
    50HZ/60HZ
    9.5 13.1 16.3 19 26.2 32.6 38 50.2 49 66
    KW (60HZ) 11.4 15.72 19.56 22.8 31.44 39.12 45.6 60.24 58.8 79.2
    Input power (KW) 3.07 3.87 5.3 5.95 7.75 10.6 11.9 16.25 15.85 19.71
    Maximum current (A) 7.5 9.4 12.9 14.4 18.8 25.7 28.9 39.4 38.2 47.8
    Power 3PH~380V/415V~50HZ/60HZ (3PH~200V/220V 50HZ/60HZ)
    Refrigerant Name R22/R407C/134a/404A/410A
    Control Capillary/external balance of thermal expansion valve
    Compressor Type Hermetic scroll (piston)
    Power (KW) 2.7 3.5 4.55 5.2 7 4.55×2 5.2×2 11.25 5.55×2 8.96×2
    Condenser Type Efficient aluminum finned copper sleeve + Stainless steel plate evaporator
    Cooling air flow (m³/h) 2.1 2.9 3.6 4.2 5.7 7.1 8.3 11 10.8 14.4
    Cooling air flow (60HZ) 2.4 3.3 4.1 4.8 6.6 8.3 9.6 12.8 12.5 16.7
    Diameter (inch) 1-1/2” 1-1/2” 1-1/2” 1-1/2” 1-1/2” 1-1/2” 1-1/2” 2” 2” 2”
    Evaporator Type Tank coil/Dry shell and tube / Stainless steel plate evaporator
    Frozen water (m³/h) 1.63 2.25 2.8 3.27 4.5 5.6 6.53 8.63 8.43 11.35
    Frozen water (60HZ) 1.96 2.7 3.36 3.92 5.4 6.73 7.84 10.36 10.1 13.62
    Capacity (L) 60 60 60 90 150 200 200 330 330 330
    Diameter (inch) 1” 1” 1” 1” 1-1/2” 2” 2” 2” 2” 2”
    Pump Power (KW) 0.37 0.37 0.75 0.75 0.75 0.75 0.75 1.5 1.5 1.5
    Maximum lift (m) 22 22 30 30 25 25 25 28 28 28
    Maximum flow (m³/h) 5.4 5.4 8.1 8.1 8.1 13.5 13.5 25.2 25.2 25.2
    Security Compressor motor overheating protection, overload protection device unit, high and low pressure protection device, frost protection devices, power reverse phase/phase protection, exhaust temperature protection, over-temperature protection, flow switches

    Parameter Table (2)

    Type PC-25WC(D) PC-30WC(D) PC-30WC(T) PC-40WC(D) PC-40WC(F) PC-50WC(D) PC-50WC(F)
    Refrigerating capacity Kcal/h
    50HZ/60HZ
    66048 83420 85140 114036 113520 134504 132096
    Kcal/h (60HZ) 79258 100104 102168 136843 136224 161405 158515
    KW
    50HZ/60HZ
    76.8 98 99 132.6 132 156.4 153.6
    KW (60HZ) 92.16 116.4 118.8 159.12 158.4 187.68 184.32
    Input power (KW) 23.8 30.99 30.63 41.31 39.59 52.7 48.7
    Maximum current (A) 61.7 75.2 74.8 100.3 96.6 127.9 119.7
    Power 3PH~380V/415V~50HZ/60HZ (3PH~200V/220V 50HZ/60HZ)
    Refrigerant Name R22/R407C/134a/404A/410A
    Control Capillary/external balance of thermal expansion valve
    Compressor Type Hermetic scroll (piston)
    Power (KW) 10.8×2 13.62×2 8.96×3 13.62×2 18.78×4 23.6×2 10.8×4
    Condenser Type Efficient aluminum finned copper sleeve + Stainless steel plate evaporator
    Cooling air flow (m³/h) 17 21.4 21.7 29.3 28.9 35 33.9
    Cooling air flow (60HZ) 19.6 24.7 25.1 33.8 34.4 40.4 39.1
    Diameter (inch) 2” 2-1/2” 2-1/2” 3” 3” 3” 3”
    Evaporator Type Tank coil/Dry shell and tube / Stainless steel plate evaporator
    Frozen water (m³/h) 13.21 16.68 17.02 22.8 22.7 26.9 26.41
    Frozen water (60HZ) 15.85 20.02 20.43 27.36 27.24 32.27 31.7
    Capacity (L) 350 450 450 580 580 620 620
    Diameter (inch) 2” 2-1/2” 2-1/2” 3” 3” 3” 3”
    Pump Power (KW) 2.2 2.2 2.2 3.7 3.7 5.5 5.5
    Maximum lift (m) 28 30 30 30 30 32 32
    Maximum flow (m³/h) 25.2 36 36 36 36 40 40
    Security Compressor motor overheating protection, overload protection device unit, high and low pressure protection device, frost protection devices, power reverse phase/phase protection, exhaust temperature protection, over-temperature protection, flow switches

    Notes

    1. Cooling capacity is based on: chilled water inlet and outlet water temperature 12℃/7℃, the cooling air inlet temperature of 30℃/35℃.

    2. Scope of work: chilled water temperature range: 5℃ to 35℃; chilled water out of the water temperature: 3℃ to 18℃.

    In condensing, the ambient temperature is not higher than 35℃ using (non-standard chilled ambient temperature maximum temperature of 5℃, need to order production).

    These models can be customized according to customer to produce custom-made.

    Specification Dimensions above are subject to change without notice.

    Frequently Asked Questions

    Q1: What are the core design advantages of these chiller units?

    The units feature a highly compact and lightweight structure with imported hermetic scroll compressors. They offer smooth, low-vibration operation with 20%-30% higher efficiency than reciprocating compressors, alongside intelligent microcomputer control and multiple safety protections.

    Q2: What is the standard temperature range for the chilled water?

    The standard operating range for chilled water temperature is 5℃ to 35℃, and the outlet water temperature range is 3℃ to 18℃.

    Q3: Under what conditions is the cooling capacity calculated?

    The cooling capacity is calculated based on a chilled water inlet/outlet temperature of 12℃/7℃, and a cooling air inlet temperature of 30℃/35℃.

    Q4: What safety protections do the microcomputer controllers provide?

    The units are equipped with multiple protection modules including compressor coil overcurrent protection, pump overcurrent protection, cold water flow switches, low cooling protection, high-temperature water protection, compressor overload, frequent start/stop protection, abnormal voltage protection, and high/low pressure protection.

    Q5: Can these chiller units be customized for specific requirements?

    Yes, all models can be customized according to specific customer requirements. For example, if you need a non-standard chilled ambient temperature (maximum of 5℃), it can be ordered and custom-produced.

    Q6: How difficult is the installation process?

    Installation is very simple. All components are pre-installed and run-tested at the factory, with refrigerants and refrigeration oils already charged. Users only need to connect the water circuit and electrical circuit to put the unit into use.

    Leave Your Message